で 1822 説明済み: HEPAおよびULPAフィルターのテスト

共有:

目次

で 1822 is the European standard used to classify high-efficiency air filters for ventilation, air-conditioning and technical processes such as cleanrooms and pharmaceutical manufacturing.

The standard covers three filter groups:

  • Group E: EPAフィルター
  • グループH: HEPAフィルター
  • Group U: ULPA filters

This article refers to EN 1822-1:2019, which defines classification, performance testing and marking. The detailed procedures for aerosol generation, 粒子測定, filter-media testing, filter-element leakage and overall efficiency are referenced through ISO 29463 部品 2 に 5.

Why Does EN 1822 Use MPPS?

で 1822 evaluates filters at the most penetrating particle size, またはMPPS.

MPPS is the particle size at which a particular filter medium has its lowest filtration efficiency under the specified test conditions. It is determined from a fractional-efficiency curve rather than assumed to be one fixed particle diameter.

For many glass-fibre filter media, MPPS is often found within a submicrometre range. しかし, it should not automatically be stated as 0.3 μm. The actual result depends on the filter medium, face velocity and particle-capture mechanisms.

Testing only at a fixed 0.3 µm channel may be useful for a validated production quality-control method, but it is not automatically equivalent to formal EN 1822 MPPSでの分類.

で 1822 Filter Classes

で 1822 classifies filters according to their efficiency or penetration at MPPS.

フィルターグループクラスMPPSでの最小積分効率Minimum local efficiency at MPPS
EPAE1085%分類には使用されません
EPAE1195%分類には使用されません
EPAE1299.5%分類には使用されません
HEPAH1399.95%99.75%
HEPAH1499.995%99.975%
ULPAU1599.9995%99.9975%
ULPAU1699.99995%99.99975%
ULPAU1799.999995%99.9999%

Group E filters are classified using integral efficiency and are not leak-tested for classification purposes.

Groups H and U require both integral performance and compliance with the applicable local penetration limit. The standard does not require physically “zero leakage.” It requires that local penetration does not exceed the limit specified for the relevant class and method.

Three Different Test Tasks

A complete EN 1822 evaluation involves related but distinct test tasks.

1. Filter-Media Testing

A flat-sheet media sample is tested across a particle-size range at the specified media velocity. The fractional-efficiency curve is used to identify MPPS and evaluate the performance of the filter medium.

Media testing is useful during material selection and product development, but it does not classify the finished filter.

Pleating, adhesive application, framing, sealing and handling can all affect the performance of the completed product.

2. Integral Filter Efficiency

The finished filter is tested at its nominal airflow. Upstream and downstream particle concentrations are measured to determine the average efficiency or penetration of the complete filter element at MPPS.

Pressure drop is also recorded at the nominal airflow.

Integral efficiency represents the average performance of the whole filter. A filter can meet its integral efficiency requirement and still contain a localized defect.

3. ローカルリークテスト

Local testing checks the downstream filter surface and relevant sealing areas for points where penetration exceeds the permitted limit.

Possible defects include:

  • Damage or pinholes in the filter medium
  • Adhesive discontinuities
  • Leakage between the media pack and frame
  • Manufacturing or handling damage

In a particle-counting scan test, a sampling probe moves across the downstream face of the filter. Reliable results depend on complete scanning coverage, controlled probe speed, プローブ距離, sampling flow and stable upstream aerosol concentration.

A scan test is therefore more than moving a particle counter across the filter surface.

What Controls the Accuracy of the Test?

Reliable EN 1822 testing requires the complete measurement system to operate under controlled conditions.

Important factors include:

  • Stable test airflow
  • Correct filter installation and sealing
  • Suitable aerosol generation at the required MPPS
  • Uniform upstream aerosol concentration
  • 代表的な上流および下流のサンプリング
  • Particle-counter sensitivity and concentration range
  • Appropriate dilution when required
  • Low background particle concentration
  • Controlled scanning speed and probe geometry
  • Complete scan coverage
  • Correct calculation and reporting logic

The required detector sensitivity becomes increasingly demanding from H13 through U17. Equipment suitable for routine H13 production testing is not automatically capable of accurately evaluating U16 or U17 filters.

Factory Testing and Installed-System Testing Are Different

で 1822 classification is performed on the filter element under defined test conditions.

An installed-filter integrity test checks the filter after installation in a cleanroom, air-handling unit or other system. It can detect bypass leakage through the gasket, ジェルシール, mounting frame or housing.

Installed integrity testing does not replace the manufacturer’s factory classification test. Likewise, a factory filter scanner and a portable photometer used for field integrity testing are not the same type of equipment.

What Should Be Defined Before Selecting Equipment?

Before selecting an EN 1822 テストシステム, 確認する:

  1. The required filter class
  2. フィルターの最大寸法
  3. Nominal airflow and pressure-drop range
  4. Expected MPPS range
  5. テストエアロゾル
  6. Required particle-measurement sensitivity
  7. Whether the task is media testing, 積分効率, leak scanning or a combination
  8. Required production throughput and automation
  9. Report format and customer acceptance criteria

Stating only that equipment “supports EN 1822” is not enough. The actual test scope, filter class and measurement capability must be defined.

SCPUR provides separate solutions for flat-sheet filter-media evaluation and factory testing of finished EPA, HEPAおよびULPAフィルター. The SC-L8023/U series supports controlled factory scanning and production testing according to the required filter size, 気流, particle-measurement range and test procedure.

Recommended Test System:SC-L8023U HEPA & ULPA Automatic Filter Scanning System

で 1822

連絡する

出発前に...

自分のプロジェクトにどの国際標準が適用されるかわからない? 当社の 10 年間の業界専門知識に基づいた個別の技術評価については、当社の上級エンジニアと相談してください。.

*私たちはあなたの秘密を尊重し、すべての情報が保護されます.

世界標準の試験システムで品質を検証

当社の専門家がお客様に合わせてカスタム ソリューションを設計いたします. あなたのプロジェクトについて教えてください, あなたの品質を正確かつ迅速に検証しましょう.

カスタムR&D & カスタマイズされたソリューション

カスタムR&D & カスタマイズされたソリューション

世界標準への準拠

世界標準への準拠

100% 自社開発のソフトウェアシステム

100% 自社開発ソフトウェアシステム

リモート校正 & グローバルサポート

リモート校正 & グローバルサポート

お問い合わせ

*私たちはあなたの秘密を尊重し、すべての情報が保護されます.

This page has been automatically translated from the English original for convenience. Product models, standards, numerical values and technical limits should be verified against the English version. Please contact SCPUR for project-specific confirmation.